ADD TO WISHLIST

Ceiling Concealed Duct Unit (Low Static) 5.6kW ARNU18GL2G4
See Retailer for Pricing

Limited Quantity Sale

Available QTY 0
  • vip-price-message
    (ARNU18GL2G4)
    $
    $
    LG Members Price
Total

component-OBScountrySelectDesc

See Retailer for Pricing

Limited Quantity Sale

Available QTY 0
  • vip-price-message
    (ARNU18GL2G4)
    $
    $
    LG Members Price
Total
Ceiling Concealed Duct Unit (Low Static) 5.6kW ARNU18GL2G4
CAPACITY
  • Cooling - kW
    5.6
    Cooling - kcal/h
    4,800
  • Cooling - Btu/h
    19,100
    Heating - kW
    6.3
  • Heating - kcal/h
    5,400
    Heating - Btu/h
    21,500
POWER INPUT
  • Power Input(H / M / L) - W
    71 / 56 / 41
CASING
  • Casing
    Galvanized Steel Plate
DIMENSIONS(W × H × D)
  • Body - ㎜
    900 × 190 × 700
    Body - inch
    35-7/16 × 7-15/32 × 27-9/16
COIL
  • Rows × Columns × FPI
    2 × 11 × 18
    Face Area - m²
    0.17
FAN
  • Type
    Sirocco Fan
    Motor Output × Number - W × No.
    19 × 1, 5 × 1
  • Running Current - A
    0.76
    Air Flow Rate(H / M / L) (High Mode-Factory Set) - m³/min
    15.0 / 12.5 / 10.0
  • Air Flow Rate(H / M / L) (High Mode-Factory Set) - ft³/min
    530 / 450 / 360
    External Static Pressure (High Mode) - ㎜Aq(Pa)
    2.54 (25)
  • Air Flow Rate (H / M / L) (Standard Mode) - m³/min
    15.0 / 12.5 / 10.0
    Air Flow Rate (H / M / L) (Standard Mode) - ft³/min
    530 / 450 / 360
  • External Static Pressure (Standard Mode) - ㎜Aq(Pa)
    0 (0)
    Drive
    Direct
  • Motor type
    BLDC
TEMPERATURE CONTROL
  • Temperature Control
    Microprocessor, Thermostat for cooling and heating
SOUND ABSORBING THERMAL INSULATION MATERIAL
  • Sound Absorbing Thermal Insulation Material
    Foamed polystyrene
SAFETY DEVICE
  • Safety Device
    Fuse
PIPE CONNECTIONS
  • Liquid Side - ㎜(inch)
    Ø 6.35 (1/4)
    Gas Side - ㎜(inch)
    Ø 12.7 (1/2)
  • Drain Pipe(Internal Dia.) - ㎜(inch)
    Ø 25.4 (1)
NET WEIGHT
  • Body - kg(lbs)
    23 (50.7)
SOUND PRESSURE LEVELS
  • H / M / L - dB(A)
    35 / 32 / 29
SOUND POWER LEVELS
  • H / M / L - dB(A)
    56 / 54 / 51
POWER SUPPLY
  • Power Supply - Ø, V, Hz
    1, 220-240, 50
    1, 220, 60
REFRIGERANT CONTROL
  • Refrigerant Control
    EEV
TRANSMISSION CABLE
  • Transmission Cable - ㎟ × Cores
    1.0-1.5 × 2C

Compare