1. No risk of pipe freezing

    Refrigerant pipe robust to cold ensures no potential risk of pipe freezing even during prolonged blackouts.

  2. Remarkable performance in cold

    Wide operation range ensures remarkable heating performance even in an extremely cold weather.

  3. Low noise level

    Noise reduction technology provides quieter and more comfortable experience, increasing installation flexibility in urban areas.

All Spec

DIMENSION

  • Indoor unit (W × H × D) (mm)

    490 × 850 × 315

  • Outdoor unit (W × H × D) (mm)

    950 × 834 × 330

EXTERIOR

  • Indoor unit (Color / RAL code)

    Noble white / RAL 9016

  • Outdoor unit (Color / RAL code)

    Warm gray / RAL 7044

NOMINAL CAPACITY AND COP (A+2/W+35)

  • COP

    3.50

  • Heating capacity (kW)

    5.40

NOMINAL CAPACITY AND COP (A+7/W+35)

  • COP

    4.65

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND COP (A+7/W+55)

  • COP

    2.70

  • Heating capacity (kW)

    5.50

NOMINAL CAPACITY AND EER (A+35/W+18)

  • Cooling capacity (kW)

    9.00

  • EER

    4.20

NOMINAL CAPACITY AND EER (A+35/W+7)

  • Cooling capacity (kW)

    9.00

  • EER

    2.60

OPERATION RANGE (LEAVING WATER TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 27

  • DHW (Min. ~ Max.) (℃)

    15 ~ 80

  • Heating (Min. ~ Max.) (℃)

    15 ~ 65

OPERATION RANGE (OUTDOOR AIR TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 48

  • Heating & DHW (Min. ~ Max.) (℃)

    -25 ~ 35

PIPING CONNECTIONS (REF./OUTDOOR UNIT)

  • Gas (mm (inch))

    Ø 15.88 (5/8)

  • Length standard / Max. (m)

    5 / 50

  • Level difference Max. (m)

    30

  • Liquid (mm (inch))

    Ø 9.52 (3/8)

  • Mass of additional ref. charge (g/m)

    40

  • Max. length without additional charge (m)

    10

PIPING CONNECTIONS (WATER/INDOOR UNIT)

  • Inlet diameter for space heating (inch)

    Male PT 1"

  • Outlet diameter for space heating (inch)

    Male PT 1"

POWER SUPPLY

  • Voltage, phase, frequency (V, Ø, Hz)

    220-240, 1, 50

REFRIGERANT

  • GWP

    675

  • Precharged amount (g)

    1,500

  • Type

    R32

SEASONAL EFFICIENCY DATA (HEATING)

  • Seasonal space heating efficiency (ηS) (35℃ / 55℃)

    183 / 126

  • SCOP (35℃ / 55℃)

    4.65 / 3.23

  • Seasonal space heating eff. class (35℃ / 55℃)

    A+++/A++

SOUND POWER LEVEL (INDOOR UNIT)

  • Rated (dB(A))

    44

SOUND POWER LEVEL (OUTDOOR UNIT)

  • Rated / low noise mode (dB(A))

    60 / 58

SOUND PRESSURE LEVEL AT 1M (INDOOR UNIT, CONVERT USING SWL)

  • Rated (dB(A))

    36

SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)

  • Rated / low noise mode (dB(A))

    38 / 36

WEIGHT

  • Indoor unit (Empty) (kg)

    38.1

  • Outdoor unit (Empty) (kg)

    60.0

COMPLIANCE INFORMATION

The safety information for accessories is included with the safety information for the product and is not provided separately.

To access more technical documentation and downloads, please visit the LG B2B Partner Portal.