We use cookies, including cookies from third parties, to enhance your user experience and the effectiveness of our marketing activities. These cookies are performance, analytics and advertising cookies, please see our Privacy and Cookie policy for further information. If you agree to all of our cookies select “Accept all” or select “Cookie Settings” to see which cookies we use and choose which ones you would like to accept.
14kw R290 Monobloc Air to water heat pump & Hydro Unit , 3 Phase,with low GWP & quiet operation ,75 degree celcius max heating
14kw R290 Monobloc Air to water heat pump & Hydro Unit , 3 Phase,with low GWP & quiet operation ,75 degree celcius max heating
Key Features
- Natural refrigerant R290 with low GWP (3)
- No refrigerant piping work
- ErP energy label class LWT A+++/A+++ (35°C/55°C)
- Refined gray design that adapts to various surroundings
- High leaving water temperature up to 75°C and wide operating range down to -28°C ambient temperature
- One of the quietest models on the market (51 dB(A) for 14 kW model)
* All tests were conducted according to LG's internal test policy and environment.
* Product’s lifecycle might vary depends on actual usage environment.
* LG BECON cloud service availability can be varied by each country.
Gallery
All Spec
SEASONAL EFFICIENCY DATA (HEATING)
-
Seasonal space heating eff. class (35℃ / 55℃)
A+++/A+++
-
Seasonal space heating efficiency (ηS) (35℃ / 55℃)
212 / 155
-
SCOP (35℃ / 55℃)
5.38 / 3.96
NOMINAL CAPACITY AND COP (A+7/W+35)
-
Heating capacity (kW)
14.00
-
COP
4.50
NOMINAL CAPACITY AND COP (A+2/W+35)
-
Heating capacity (kW)
14.00
-
COP
3.61
NOMINAL CAPACITY AND COP (A-7/W+35)
-
Heating capacity (kW)
13.00
-
COP
3.21
NOMINAL CAPACITY AND COP (A+7/W+55)
-
Heating capacity (kW)
11.00
-
COP
3.25
NOMINAL CAPACITY AND COP (A-7/W+55)
-
Heating capacity (kW)
10.30
-
COP
2.28
NOMINAL CAPACITY AND EER (A+35/W+18)
-
Cooling capacity (kW)
12.00
-
EER
3.70
NOMINAL CAPACITY AND EER (A+35/W+7)
-
Cooling capacity (kW)
12.00
-
EER
2.99
OPERATION RANGE (OUTDOOR AIR TEMPERATURE)
-
Heating & DHW (Min. ~ Max.) (℃)
-28 ~ 35
-
Cooling (Min. ~ Max.) (℃)
5 ~ 48
OPERATION RANGE (LEAVING WATER TEMPERATURE)
-
Heating (Min. ~ Max.) (℃)
15 ~ 75
-
Cooling (Min. ~ Max.) (℃)
5 ~ 27
-
DHW (Min. ~ Max.) (℃)
15 ~ 80
REFRIGERANT
-
Type
R290
-
GWP
3
-
Precharged amount (g)
1,200
PIPING CONNECTIONS (WATER/OUTDOOR UNIT)
-
Inlet diameter (inch)
Male PT 1"
-
Outlet diameter (inch)
Male PT 1"
PIPING CONNECTIONS (WATER/INDOOR UNIT)
-
Inlet/outlet diameter for ODU connection (inch)
Male PT 1"
-
Inlet/outlet diameter for space heating (inch)
Male PT 1"
SOUND POWER LEVEL (OUTDOOR UNIT)
-
Rated / low noise mode (dB(A))
51 / 50
SOUND POWER LEVEL (INDOOR UNIT)
-
Rated (dB(A))
39
SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)
-
Rated / low noise mode (dB(A))
29 / 28
SOUND PRESSURE LEVEL AT 1M (INDOOR UNIT, CONVERT USING SWL)
-
Rated (dB(A))
31
DIMENSION
-
Outdoor unit (W × H × D) (mm)
1,560 x 1,019 x 520
-
Indoor unit (W × H × D) (mm)
490 x 850 x 315
WEIGHT
-
Outdoor unit (Empty) (kg)
181.0
-
Indoor unit (Empty) (kg)
31.0
EXTERIOR
-
Color of outdoor unit chassis (Color / RAL code)
Dawn gray / RAL 7037
-
Indoor unit (Color / RAL code)
Noble white / RAL 9016
-
Color of outdoor unit front grille (Color / RAL code)
Dark dawn gray / RAL 7012
POWER SUPPLY
-
Voltage, phase, frequency for outdoor unit (V, Ø, Hz)
380 ~ 415, 3, 50
-
Voltage, phase, frequency for indoor unit (V, Ø, Hz)
220 ~ 240, 1, 50
COMPLIANCE INFORMATION
-
extension:pdf
-
extension:pdf
-
extension:pdf
-
extension:pdf
-
extension:pdf
-
Manual& Software
Download product manuals and latest software for your LG product.
-
Troubleshoot
Find helpful videos and information about your product systems.
-
Warranty
Check LG warranty information here.
-
Part & Accessory
Discover accessories for LG products.
-
Product Support
Find manual, troubleshoot and warranty of your LG product.
-
Order Support
Track your order and check order FAQ.
To access more technical documentation and downloads, please visit the LG B2B Partner Portal.